The Hioki 3169 Clamp On Power Tester allows measurement of single-phase to three-phase 4-wire circuits with a single unit. In addition to measuring standard parameters such as voltage, current, power, power factor, and integrated values, the 3169 can simultaneously perform demand measurements required for carrying out power management and energy-saving measures, as well as harmonic measurements.
The Hioki 3169 features PC card data storage, and comes equipped with an RS-232C interface for PC communications. With greater data processing speeds, it is possible to measure the power of just a few cycles, enabling more detailed and effective energy-saving measures for equipment.
The Hioki 3169 is ideal for users who want to achieve close control over energy-saving management activities and measures.
All Optional 3169 PRO Kits Include:
-3169-20 Power Demand Analyzer with no Analog Output or 3169-21 Power Demand Analyzer with Analog Output
-4 Sensors
-Voltage Cable Set
-9625 PC Software
-Hard Carrying Case
-256MB PC Card
Please note: Current and power cannot be measured using the 3169 on its own. To perform current and power measurement, you must select a current clamp-on sensor.
Measurement Line & Number of Circuits | Single-phase 2-wires (4 circuits), Single-phase 3-wires (2 circuits), Three-phases 3-wires (2 or 1 circuit), and Three-phases 4-wires (1 circuit) Note: 50 or 60 Hz, and that share the same voltage line |
Measurement Items | Voltage, Current, Active/ reactive/ apparent power, Active/ reactive power integration, Power factor, Frequency, Harmonic waveform value |
Voltage Ranges | 150.00 V to 600.00 V AC, 3 ranges |
Current Ranges | 500.00 mA to 5.0000 kA AC (depends on current sensor in use) |
Power Ranges | 75.000 W to 900.00 kW (depends on combination of voltage, current range, and measurement line) |
Basic Accuracy | AC Voltage: ±0.2 % rdg. ±0.1 % f.s. AC Current: ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy Active power: ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy (at power factor = 1) CLAMP ON SENSOR 9661: ±0.3 % rdg. ±0.01 % f.s. (different from each model) |
Measurement Method | Digital sampling, PLL synchronization or 50/60 Hz fixed clock |
Basic Accuracy | Active power: ±0.2% rdg. ±0.1% f.s. + clamp-on sensor accuracy (at 45 to 66 Hz) |
Display Refresh Rate | 2 times /sec (except when using a PC card while accessing the internal memory, or when performing RS-232C communications) |
Data Save Interval | Standard interval: 1 sec to 30 sec, 1 minute to 60 minutes, 13 selects Fast interval: A single waveform, or 0.1, 0.2, or 0.5 sec (at instant value only) |
Frequency Characteristics | Fundamental waveforms up to the 50th order ±3% f.s. + measurement accuracy (of a 45 to 66 Hz fundamental waveform) |
Other Functions | Error connect check, language selection, display hold, setting backup, power shut off management, key lock, [3169-21 only] D/A output 4 channels, ±5 V DC f.s.) |
Power Supply | 100 to 240 V AC, 50/60 Hz, 30 VA max. |
Dimensions, Mass | 210 mm (8.27 in) W × 160 mm (6.30 in) H × 60 mm (2.36 in) D, 1.2 kg (42.3 oz) |
Supplied Accessories | VOLTAGE CORD L9438-53 ×1 (Black/ Red/ Yellow/ Blue), Power cord ×1, Instruction Manual ×1, Quick Start Manual ×1, CD-R ×1 (RS-232C interface operating manual) ×1, Input cord label ×1, CONNECTION CABLE 9441 ×1 (for the 3169-21 only) |